A 6,500 Sq. Ft. ISO Class 8 Cleanroom Retrofitted Into a Plant in London, Ontario

The challenge. The building's own drawings did not match the building. Existing walls and columns, a rooftop unit already in place, and very little room left for new ducting.

The result. One 6,500 sq. ft. ISO Class 8 room, designed around what was actually there rather than what the drawings showed, and certified to ISO 14644-1 on handover.

INDUSTRY

Liquid silicone rubber injection molding

APPLICATION

Oral solid dose manufacturing and packaging

PROJECT TYPE

Renovation, ISO Class 8 cleanroom added inside an operating plant

CLEANROOM AREA

6,500 sq. ft. One room, approximately 100 ft by 65 ft, 14 ft high

CLASSIFICATION

ISO Class 8 to ISO 14644-1, certification passed

SCOPE

HVAC design, structural and panel shop drawings, supply and installation of the cleanroom

TIMELINE

Design: June to September 2025

Installation: January to June 2026

Why Liquid Silicone Rubber Molding Needs an ISO Class 8 Cleanroom

Silicone keeps whatever lands on it. Liquid silicone rubber is tacky before it cures and it holds a static charge, so airborne particulate does not brush off a part or a tool face, it sticks. Once the part cures, that particle is no longer on the surface, it is in the part. There is no cleaning stage that recovers it. The part is scrap, and if the contamination is in the tool, so is the next one.

The customers drive the rest. Molded silicone components go into medical devices, fluid handling and sealing applications, and the people buying them audit the environment the parts were made in. They are not looking for a tidy corner of a plant. They want a classified space with a number attached to it, and evidence that the number was met by test rather than by assertion.

The complication here was that the plant was already running. The cleanroom had to be built inside a working molding facility, fed by a rooftop unit that was already installed, threaded between walls and columns that were staying, and squeezed into the ducting space that was left over. Nothing could be cleared and started again.

What the room had to deliver

  • ISO Class 8 to ISO 14644-1, certified
  • Positive pressure against the plant around it
  • Filtered supply through ceiling fan filter units
  • A sealed, cleanable envelope throughout
  • 14 ft height for machines and material handling
  • One clear span, with no columns added
  • Built without stopping production next door
ISO Class 8 cleanroom built inside a working injection molding plant in London, Ontario
A 6,500 sq. ft. ISO Class 8 room, built inside a plant that never stopped running.

Scope of Work: Design, Shop Drawings and a Complete Cleanroom Envelope

ACH designed the ventilation, designed the structure, drew every panel, and then supplied and installed the cleanroom itself. Three pieces of work that are usually spread across three companies, held together here by one team working to one set of drawings.

HVAC and Ventilation Design

Supply ductwork distributing filtered air to the ISO Class 8 cleanroom in a London, Ontario molding plant
Supply ductwork distributing filtered air across the 6,500 sq. ft. room.

ACH designed the ventilation and ducting for the cleanroom around the air handling unit the plant already had on its roof, and around the ducting space that was actually available rather than the space the drawings showed.

  • Ventilation design for the full 6,500 sq. ft. room
  • Ducting layout within the available ceiling space
  • Design around the existing rooftop air handling unit
  • Supply distribution to the ceiling fan filter units
  • Return air strategy for a positive pressure room
  • Air change rate set to hold ISO Class 8 in operation
  • Drawings issued for the mechanical trade to install

Structure and Shop Drawings

ISO Class 8 cleanroom shop drawing isometric showing the walkable ceiling, HEPA units and lighting layout
Every panel, light and HEPA unit located before anything was fabricated.

A walkable ceiling has to be carried by a building that was never designed to hold one. ACH produced the structural design for it and the shop drawings for every panel, set out from site survey rather than from the existing drawings.

  • Structural design for the walkable ceiling
  • Loads checked against existing columns and walls
  • Shop drawings for every wall and ceiling panel
  • Panel layout set out from measured site survey
  • Door, grille and light openings coordinated
  • Interfaces with the existing structure detailed
  • Drawings reissued as the scope developed

Supply and Installation

Walkable cleanroom ceiling and LED lighting being installed in a London, Ontario injection molding plant
The walkable ceiling going in, with LED lighting set flush into the grid.

ACH supplied and installed the complete cleanroom envelope, from the liner panel walls through to the trims, so one team was accountable for how the room went together and for how it performed when it was finally tested.

  • Cleanroom wall liner panel system
  • Walkable ceiling system supplied and installed
  • Cleanroom doors and frames
  • Fan filter units set into the ceiling grid
  • LED lighting integrated flush with the ceiling
  • Return air grilles positioned to the design
  • Coving and trims throughout the room

Where the scope ended. HVAC on this project was a design commission. ACH produced the ventilation and ducting design, and the mechanical trade working for the client carried out the installation. Vision panels and flooring were outside ACH's scope as well. The cleanroom envelope, the walkable ceiling and everything fitted into them were supplied and installed by ACH.

The Challenges of Building a Certified Cleanroom Inside a Working Plant

This room was not drawn on a clear site. It was fitted into a plant that was already running, around equipment that was already installed, inside structure that was not moving, and it still had to pass ISO Class 8 certification at the end of it.

The drawings did not match the building

The existing building drawings were not accurate. Every dimension that mattered was taken again by survey, and the panel layout was set out from measured reality rather than from the record set.

Existing structure and no spare ceiling space

The envelope had to be threaded between walls and columns that were not moving, and the duct layout had to fit the ceiling space that was left over rather than the space a clear building would have offered.

Existing manufacturing plant in London, Ontario before the ISO Class 8 cleanroom retrofit
The space as ACH found it. Existing columns, existing walls, an air handling unit already on the roof, and whatever ceiling space was left over.

An air handling unit already on the roof

The ventilation design had to work with the unit the plant already had. There was no new plant to size and no second attempt at it. ISO Class 8 had to be reached with the air that unit could deliver.

A panel system new to the market

The liner panel system used here was new. ACH worked the details out with it on a live site and certified with it, which is a harder exercise than installing a system the whole trade has built a hundred times.

Several trades in one room at once

The cleanroom went in alongside other contractors working in the same space to their own programmes. Sequencing and interfaces had to be agreed, and then agreed again as the work moved around them.

A scope that kept developing

Requirements firmed up as the design and the installation progressed. Drawings were reissued and work was resequenced to take the changes in as they came, rather than stacking them up for the end.

The Solution: Survey, Shop Drawings and One Accountable Team

None of these problems were solved by working harder on site. They were solved earlier, by measuring the building instead of believing it, by designing to the plant that was already there, and by drawing every panel before any of them were made.

Completed ISO Class 8 cleanroom for injection molding in London, Ontario
The finished room. One clear span of 6,500 sq. ft., held at positive pressure and certified to ISO Class 8.

Measured before anything was drawn

Nothing was taken on trust from the record drawings. The building was surveyed, and the panel layout and ceiling setting out were worked from those dimensions, so what arrived on site fitted what was actually there.

An envelope planned around the structure

Walls and ceiling were set out to the existing column grid, and the duct routing was resolved inside the ceiling space that was genuinely available rather than the space the old drawings appeared to offer.

One team across design and installation

Because ACH drew the room and then installed it, interfaces with the other trades were settled against drawings ACH owned, and the sequence could be changed without a second company having to agree it first.

A design built around the existing unit

The ventilation design started from the air the rooftop unit could already deliver and distributed it through ceiling fan filter units, so ISO Class 8 could be held without the client having to replace the plant.

Shop drawings for every single panel

Every wall and ceiling panel was drawn before it was made, with door, grille and light openings located on the drawing, so a panel system new to the market went in to a set of details instead of being resolved on site.

Changes absorbed as they arrived

Each change requested through design and installation was taken in as it came, with drawings reissued and work resequenced, so the programme carried the changes rather than ending in a list of outstanding items.

The Result: A Certified ISO Class 8 Cleanroom Inside an Existing Plant

A working injection molding plant in London, Ontario gained 6,500 sq. ft. of classified production space without a new building, without new air handling plant, and without the structure around it being cleared out of the way.

6500

Square feet of ISO Class 8 cleanroom added inside an existing plant

ISO 8

Classification to ISO 14644-1, certification passed on completion

14 ft

Height across a single open span of roughly 100 ft by 65 ft

1

Room, one team and one set of drawings from design to handover

The room passed ISO Class 8 certification. On a retrofit that is not a formality. The classification depends on filtration, on air change rate and on holding the room positive against everything around it, and all three had to be achieved with an air handling unit that was chosen years earlier for a different job.

It was won at the drawing stage rather than on site. The building was surveyed instead of being taken on trust, every panel was drawn before it was made, and the openings for doors, lights and HEPA units were located on the drawing. By the time the panels arrived there was very little left to work out.

What the client has now is a classified space their own customers can audit, sitting inside the plant they already owned, served by the plant they already had. For a molder whose parts go into medical and sealing applications, that is the difference between quoting for that work and not being asked.

What was handed over

  • A cleanroom certified to ISO Class 8
  • One clear span, roughly 100 ft by 65 ft at 14 ft high
  • A walkable ceiling with HEPA fan filter units
  • LED lighting integrated flush into the ceiling
  • Doors, return grilles, coving and trims throughout
  • Ventilation and ducting design for the room
  • Shop drawings for every panel, as built

Need a classified cleanroom in a building you already have?

ACH designs and installs ISO classified cleanrooms across Canada, and most of them go into buildings that were never meant to hold one. Existing structure, existing plant, existing production. We survey what is actually there, draw every panel before it is made, and hand over a room that passes.