Cleanroom Classifications Explained: ISO 5 vs ISO 6 vs ISO 7 vs ISO 8

Cleanroom classifications chart comparing ISO 5, ISO 6, ISO 7 and ISO 8 particle limits

Cleanroom classifications are defined by ISO 14644-1, which ranks rooms from ISO 1 (cleanest) to ISO 9 by the maximum number of airborne particles allowed per cubic metre. ISO 5 allows 3,520 particles of 0.5 µm or larger per m³, ISO 6 allows 35,200, ISO 7 allows 352,000 and ISO 8 allows 3,520,000. Each class allows ten times more particles than the class above it.

Choosing a cleanroom class is the first and most expensive decision in any controlled environment project. The class sets how much filtered air the room needs, how it is laid out, what it is built from and how it is tested. Specify a class that is too strict and you pay for air and filtration you do not need. Specify one that is too loose and your product, or your audit, fails.

This guide covers every ISO cleanroom class, the full ISO 14644-1 particle limits table, how ISO classes compare with Class 100 to Class 100,000 and with EU GMP Grades A to D, typical air changes per hour for each class, and how to choose the right class for your process. For the standards behind the classes (ISO 14644-1 to 14644-5 and what each part covers), see our guide to cleanroom ISO 14644 standards.

What Is a Cleanroom Classification?

A cleanroom classification is a measure of air cleanliness: the maximum concentration of airborne particles, of given sizes, that a room may contain. The international standard is ISO 14644-1 (Classification of air cleanliness by particle concentration), which defines nine classes. The lower the number, the cleaner the room. ISO 9 is roughly ordinary room air.

Three things define a classification:

The three occupancy states

People are the largest source of particles in most cleanrooms, so a room that meets ISO 7 at rest may only meet ISO 8 in operation. Always state which occupancy state your requirement refers to.

ISO 14644-1 Particle Concentration Limits
Class ≥ 0.1 µm ≥ 0.2 µm ≥ 0.3 µm ≥ 0.5 µm ≥ 1 µm ≥ 5 µm FED-STD-209E Equivalent
ISO 1 10 2 – – – – –
ISO 2 100 24 10 4 – – –
ISO 3 1,000 237 102 35 8 – Class 1
ISO 4 10,000 2,370 1,020 352 83 – Class 10
ISO 5 100,000 23,700 10,200 3,520 832 29* Class 100
ISO 6 1,000,000 237,000 102,000 35,200 8,320 293 Class 1,000
ISO 7 – – – 352,000 83,200 2,930 Class 10,000
ISO 8 – – – 3,520,000 832,000 29,300 Class 100,000
ISO 9 – – – 35,200,000 8,320,000 293,000 Room air

“–” means no limit is specified for that particle size. *ISO 14644-1:2015 does not use the ISO 5 ≥ 5 µm count for classification because of sampling statistics; 29 is the commonly published value.

How the limits are calculated

Every value in the table comes from one formula in ISO 14644-1:

Cₙ = 10^N × (0.1 / D)^2.08.

Where Cₙ is the maximum particles per m³, N is the ISO class number and D is the particle size in µm. For example, for ISO 5 at 0.5 µm: 10⁵ × (0.1 ÷ 0.5)^2.08 ≈ 3,520 particles per m³. Each step up in class number multiplies the allowed count by ten.

ISO Classes vs Class 100 to Class 100,000 (FED-STD-209E)

Before ISO 14644-1, cleanrooms in North America were classified under the US Federal Standard 209E, which counted particles of 0.5 µm or larger per cubic foot. FED-STD-209E was replaced by ISO 14644 in 2001, but its names are still common on drawings, equipment nameplates and in conversation.

The class name was simply the particle count: a Class 100 room allowed 100 particles of 0.5 µm or larger per cubic foot, which is about 3,520 per cubic metre, the ISO 5 limit. The last column of the table above shows each equivalent:

Pharmaceutical Cleanroom Classification: EU GMP Grades A, B, C and D

Pharmaceutical cleanrooms are classified twice: by ISO class, and by grade under EU GMP Annex 1 (revised 2022, in force since August 25, 2023). Health Canada and other PIC/S regulators follow the same grades. Unlike ISO classes, each GMP grade has limits for both the at-rest and the in-operation state.

GMP Grades & ISO Equivalents
GMP Grade At Rest In Operation Typical Use
Grade A ISO 5 ISO 5 Critical zone: aseptic filling, open vials and stoppers, aseptic connections
Grade B ISO 5 ISO 7 Background room around a Grade A zone for aseptic work
Grade C ISO 7 ISO 8 Less critical steps in sterile manufacturing, such as solution preparation
Grade D ISO 8 Set by the manufacturer Handling components after washing, support areas

Microbial limits by GMP grade

GMP grades also limit living microorganisms, which ISO 14644-1 does not cover:

GMP Grades: Microbial Contamination Limits
GMP Grade Air Sample (CFU/m³) Settle Plate, 4 Hours (CFU/plate) Contact Plate (CFU/plate)
Grade A No growth No growth No growth
Grade B 10 5 5
Grade C 100 50 25
Grade D 200 100 50

Under Annex 1, every Grade A recovery must be investigated. Facilities also need a documented contamination control strategy (CCS).

Cleanroom Classification for Compounding Pharmacies (USP 797 and NAPRA)

Sterile compounding pharmacies follow USP 797 in the United States and the NAPRA Model Standards in Canada. Under USP 797:

  • The hood or isolator where compounding happens (the primary engineering control) must be ISO 5.
  • The buffer room around it must be ISO 7, with at least 30 air changes per hour.
  • The ante room must be ISO 8 (ISO 7 if it opens into a negative-pressure hazardous drug room), with at least 20 air changes per hour.
  • Each classified room is held at a positive pressure of at least 0.020 in. w.c. relative to the less clean room next to it.
  • Rooms and hoods are recertified at least every 6 months.

For the full requirements, including USP 800 hazardous drug rooms, see our USP 797 and USP 800 cleanroom requirements guide.

ISO 5 vs ISO 6 vs ISO 7 vs ISO 8 at a Glance

ISO 5 to ISO 8 Compared
ISO 5 ISO 6 ISO 7 ISO 8
Also called Class 100 Class 1,000 Class 10,000 Class 100,000
Particles ≥ 0.5 µm per m³ 3,520 35,200 352,000 3,520,000
EU GMP equivalent Grade A (and Grade B at rest) – Grade C at rest, Grade B in operation Grade D at rest, Grade C in operation
Typical air changes per hour 240–600 90–180 30–60 10–25
Airflow Unidirectional (laminar) High dilution, mixed Mixed / turbulent Mixed / turbulent
Typical uses Aseptic filling, sterile compounding hoods, semiconductor processing Electronics and semiconductor assembly, optics, some medical devices Compounding buffer rooms, medical device assembly, biotech labs Ante and gowning rooms, packaging, medical device moulding, food, cosmetics, batteries

ISO 5 Cleanroom (Class 100)

ISO 5 is the cleanest class most facilities ever need. It allows 3,520 particles of 0.5 µm or larger per m³ and usually relies on unidirectional (laminar) airflow, where HEPA-filtered air moves in parallel streams across the work area. For EU GMP Grade A zones, Annex 1 gives a guidance air velocity of 0.36–0.54 m/s at the working position.

Because a whole ISO 5 room is expensive to build and run, ISO 5 is usually created only where the product is exposed: inside a laminar flow hood, biosafety cabinet, restricted access barrier system (RABS) or isolator, placed within an ISO 7 room.

Typical uses: aseptic filling of injectables, sterile compounding hoods, cell and gene therapy processing, semiconductor wafer processing.

ISO 6 Cleanroom (Class 1,000)

ISO 6 allows 35,200 particles of 0.5 µm or larger per m³, and typically needs 90–180 air changes per hour. It sits between the critical zone and general clean production, and is common where particles smaller than the eye can see still cause defects.

Typical uses: electronics and semiconductor assembly, optics and laser components, some medical device and implant manufacturing.

ISO 7 Cleanroom (Class 10,000)

ISO 7 is the most widely specified cleanroom class. It allows 352,000 particles of 0.5 µm or larger per m³ and typically needs 30–60 air changes per hour through HEPA filters in the ceiling. Typical ISO 7 cleanroom requirements include:

  • HEPA-filtered supply air, with low-level return grilles near the floor
  • Positive pressure of about 10–15 Pa relative to adjacent less clean rooms
  • Smooth, sealed, non-shedding walls and ceilings, with coved corners for cleaning
  • An ISO 8 ante or gowning room before entry, usually with interlocked doors
  • Temperature and humidity control suited to the process and to gowned staff

Typical uses: sterile compounding buffer rooms (USP 797), medical device assembly and packaging, biotech and cell culture labs, EU GMP Grade C pharmaceutical areas.

ISO 8 Cleanroom (Class 100,000)

ISO 8 is the entry point for controlled environments. It allows 3,520,000 particles of 0.5 µm or larger per m³, ten times more than ISO 7, and typically needs 10–25 air changes per hour.

Typical uses: gowning and ante rooms, final packaging, medical device injection moulding and assembly, food and beverage, cosmetics, nutraceuticals and battery manufacturing.

ISO Criteria for Air Changes per Hour

Air changes per hour (ACH) is how many times the room’s full volume of air is replaced with filtered air each hour. ISO 14644-1 does not set air change rates; these are typical design ranges used to reach and hold each class:

ISO Class, Air Changes & Airflow Type
ISO Class FED-STD-209E Typical Air Changes Per Hour Airflow Type
ISO 1–4 Class 1–10 Designed by air velocity, not air changes Unidirectional (laminar)
ISO 5 Class 100 240–600 Unidirectional (laminar)
ISO 6 Class 1,000 90–180 High dilution, mixed
ISO 7 Class 10,000 30–60 Mixed / turbulent
ISO 8 Class 100,000 10–25 Mixed / turbulent
ISO 9 Room air Normal building ventilation Mixed

To calculate air changes per hour, divide the supply airflow per hour by the room volume. For worked examples in CFM and m³/h, see how to calculate cleanroom air changes per hour.

How to Choose the Right Cleanroom Classification

How Cleanroom Classification Is Tested and Certified

Designing for certification from the start, with test ports, accessible filters and stable pressures, avoids failed tests and costly rework at handover. For design and construction requirements, see our guide to ISO 14644-4 cleanroom design and construction, and for the full family of standards behind these classes, see cleanroom ISO 14644 standards explained.

Not Sure Which Class Your Process Needs?

Call to action box: ACH Engineering designs and builds turnkey modular cleanrooms from ISO 5 to ISO 8, from classification and layout through HVAC, construction and validation. Talk to our engineers about your process and we will recommend the right class, and the most cost-effective way to achieve it. Get a quote or call 1-866-936-4439.

Frequently Asked Questions

What are the cleanroom classifications?

ISO 14644-1 defines nine cleanroom classes, from ISO 1 (cleanest) to ISO 9 (roughly room air), based on the maximum number of airborne particles per cubic metre. ISO 5, 6, 7 and 8 are the classes most facilities use.

What is the difference between ISO 7 and ISO 8 cleanrooms?

An ISO 7 cleanroom allows 352,000 particles of 0.5 µm or larger per m³; ISO 8 allows 3,520,000, ten times more. ISO 7 typically needs 30–60 air changes per hour, ISO 8 about 10–25.

What are the requirements for an ISO 7 cleanroom?

No more than 352,000 particles of 0.5 µm or larger per m³, typically 30–60 HEPA-filtered air changes per hour, positive pressure of about 10–15 Pa over adjacent less clean rooms, cleanable non-shedding surfaces and an ISO 8 gowning room before entry.

What is an ISO 8 cleanroom used for?

Gowning and ante rooms, packaging, medical device moulding and assembly, and food, cosmetics, nutraceutical and battery manufacturing.

What is a Class 100 cleanroom in ISO terms?

Class 100 under the old FED-STD-209E is equivalent to ISO 5. Class 1,000 equals ISO 6, Class 10,000 equals ISO 7 and Class 100,000 equals ISO 8.

How are pharmaceutical cleanrooms classified?

Under EU GMP Annex 1, as Grades A to D. Grade A is ISO 5; Grade B is ISO 5 at rest and ISO 7 in operation; Grade C is ISO 7 at rest and ISO 8 in operation; Grade D is ISO 8 at rest.

What is the cleanest cleanroom class?

ISO 1, which allows only 10 particles of 0.1 µm or larger per m³. ISO 1 to ISO 4 are used mainly in semiconductor and nanotechnology manufacturing.

How many air changes per hour does each cleanroom class need?

Typical design ranges are 240-600 for ISO 5, 90-180 for ISO 6, 30-60 for ISO 7 and 10-25 for ISO 8. ISO 14644-1 sets particle limits, not air change rates.

How often must a cleanroom be reclassified?

ISO 14644-2 requires particle classification at least every 12 months. Sterile compounding pharmacies under USP 797 recertify every 6 months.

What is the difference between ISO 14644-1 and ISO 14644-2?

ISO 14644-1 sets the classes and how to classify a room. ISO 14644-2 sets how to monitor the room afterwards to prove it stays in class. See cleanroom ISO 14644 standards explained.